InfraPower PPS-02-S Q213V1 Authentication Bypass Vulnerability

Title: InfraPower PPS-02-S Q213V1 Authentication Bypass Vulnerability
Advisory ID: ZSL-2016-5374
Type: Local/Remote
Impact: Security Bypass
Risk: (4/5)
Release Date: 28.10.2016
Summary
InfraPower Manager PPS-02-S is a FREE built-in GUI of each IP dongle ( IPD-02-S only ) to remotely monitor the connected PDUs. Patented IP Dongle provides IP remote access to the PDUs by a true network IP address chain. Only 1xIP dongle allows access to max. 16 PDUs in daisy chain - which is a highly efficient cient application for saving not only the IP remote accessories cost, but also the true IP addresses required on the PDU management.
Description
The device does not properly perform authentication, allowing it to be bypassed through cookie manipulation. The vulnerable function checkLogin() in 'Function.php' checks only if the 'Login' Cookie is empty or not, allowing easy bypass of the user security mechanisms.
Vendor
Austin Hughes Electronics Ltd. - http://www.austin-hughes.com
Affected Version
Q213V1 (Firmware: V2395S)
Tested On
Linux 2.6.28 (armv5tel)
lighttpd/1.4.30-devel-1321
PHP/5.3.9
SQLite/3.7.10
Vendor Status
[27.09.2016] Vulnerability discovered.
[03.10.2016] Vendor contacted.
[04.10.2016] Vendor responds asking more details.
[04.10.2016] Sent details to the vendor.
[06.10.2016] Vendor has released a new firmware version that addresses these issues.
[28.10.2016] Public security advisory released.
PoC
infrapower_auth.txt
Credits
Vulnerability discovered by Gjoko Krstic - <gjoko@zeroscience.mk>
References
[1] https://www.exploit-db.com/exploits/40645/
[2] https://packetstormsecurity.com/files/139422
[3] https://cxsecurity.com/issue/WLB-2016100264
[4] https://exchange.xforce.ibmcloud.com/vulnerabilities/118413
Changelog
[28.10.2016] - Initial release
[31.10.2016] - Added reference [1], [2] and [3]
[02.11.2016] - Added reference [4]
Contact
Zero Science Lab

Web: http://www.zeroscience.mk
e-mail: lab@zeroscience.mk